Automation Industrielle | M-7000 modules et cartes | M-7033


Caractéristiques détaillées:
3-channel RTD Input Module Communicable via Modbus Protocol
RTD temperature range
Pt100 -100 C to +100 C a =0.00385
Pt100 0 C to +100 C a =0.00385
Pt100 0 C to +200 C a =0.00385
Pt100 0 C to +600 C a =0.00385
Pt100 -100 C to +100 C a =0.003916
Pt100 0 C to +100 C a =0.003916
Pt100 0 C to +200 C a =0.003916
Pt100 0 C to +600 C a =0.003916
Ni120 -80 C to +100 C
Ni120 0 C to +100 C
Communication Interface: ModBus Protocol
Channel : 3
Input Type :Pt , Ni
Sampling rate : 10 samples/sec
Bandwidth : 4 Hz
Wire connection: 2/3/4 wire
Accuracy: +/- 0.05% or better
Zero drift :+/- 0.3uV/ C
CMR @ 50/60 Hz: 92 dB min
NMR @50/60 Hz: 100 dB
Span drift :+/- 25ppm/ C
Power consumption : 2.2W for I-7033
3-channel RTD Input Module Communicable via Modbus Protocol
RTD temperature range
Spécifications:
Communication Interface
ModBus Protocol
Channel
3
Input Type
Pt , Ni
Sampling rate
10 samples/sec
Bandwidth
4 Hz
Wire connection
2/3/4 wire
Power consumption
2.2W for I-7033